Star-Delta Motor Starter | Details - LBM4

Recent Post

Wednesday 21 August 2019

Star-Delta Motor Starter | Details

Introduction to Star-Delta Starter 

Most induction motors are started directly on line, but when very large motors are started that way, they cause a disturbance of voltage on the supply lines due to large starting current surges. To limit the starting current surge, large induction motors are started at reduced voltage and then have full supply voltage reconnected when they run up to near rotated speed

star delta starter


A star delta starter is the most commonly used method for the starting of a 3-phase induction motor. In star delta starting an induction motor is connected in through a star connection throughout the starting period. Then once the motor reaches the required speed the motor is connected through delta connection.

Star Delta Consists Of

  1. Contactors (Main, star and delta contactors) 3 No’s (For Open State Starter) or 4 No’s (Close Transient Starter).
  2. Time relay (pull-in delayed) 1 No.
  3. Three-pole thermal overcurrent release 1 No.
  4. Fuse elements or automatic cut-outs for the main circuit 3 Nos.
  5. Fuse element or automatic cut-out for the control circuit 1No.

Working Mechanism

This is the reduced voltage starting method. Voltage reduction during star-delta starting is achieved by physically reconfiguring the motor windings as illustrated in the figure below. During starting the motor windings are connected in star configuration and this reduces the voltage across each winding 3. This also reduces the torque by a factor of three.

wroking diagram
After a period of time the winding are reconfigured as delta and the motor runs normally. Star/Delta starters are probably the most common reduced voltage starters. They are used in an attempt to reduce the start current applied to the motor during start as a means of reducing the disturbances and interference on the electrical supply.

The Star/Delta starter is manufactured from three contactors, a timer and a thermal overload. The contactors are smaller than the single contactor used in a Direct on Line starter as they are controlling winding currents only. The currents through the winding are 1/root 3 (58%) of the current in the line.

There are two contactors that are close during run, often referred to as the main contractor and the delta contactor. These are AC3 rated at 58% of the current rating of the motor. The third contactor is the star contactor and that only carries star current while the motor is connected in star.

The current in star is one third of the current in delta, so this contactor can be AC3 rated at one third (33%) of the motor rating.

Power Circuit

power circuit diagram


The main circuit breaker serves as the main power supply switch that supplies electricity to the power circuit.

The main contactor connects the reference source voltage R, Y, B to the primary terminal of the motor U1, V1, W1.

In operation, the Main Contactor (KM3) and the Star Contactor (KM1) are closed initially, and then after a period of time, the star contactor is opened, and then the delta contactor (KM2) is closed. The control of the contactors is by the timer (K1T) built into the starter. The Star and Delta are electrically interlocked and preferably mechanically interlocked as well.

 The star contactor serves to initially short the secondary terminal of the motor U2, V2, W2 for the start sequence during the initial run of the motor from standstill. This provides one third of DOL current to the motor, thus reducing the high inrush current inherent with large capacity motors at startup.

Controlling the interchanging star connection and delta connection of an AC induction motor is achieved by means of a star delta or wye delta control circuit. The control circuit consists of push button switches, auxiliary contacts and a timer.

Control Circuit For Star Delta Starter

control circuit for star delta starter
The ON push button starts the circuit by initially energizing Star Contactor Coil (KM1) of star circuit and Timer Coil (KT) circuit. When Star Contactor Coil (KM1) energized, Star Main and Auxiliary contactor change its position from NO to NC.

When Star Auxiliary Contactor (1) (which is placed on Main Contactor coil circuit ) become NO to NC it’s complete The Circuit of Main contactor Coil (KM3) so Main Contactor Coil energized and Main Contactor’s  Main and Auxiliary Contactor Change its Position from NO to NC. This sequence happens in a friction of time.

After pushing the ON push button switch, the auxiliary contact of the main contactor coil (2) which is connected in parallel across the ON push button will become NO to NC, thereby providing a latch to hold the main contactor coil activated which eventually maintains the control circuit active even after releasing the ON push button switch.

When Star Main Contactor (KM1) close its connect Motor connects on STAR and it’s connected in STAR until Time Delay Auxiliary contact KT (3) become NC to NO.

Once the time delay is reached its specified Time, the timer’s auxiliary contacts (KT)(3) in Star Coil circuit will change its position from NC to NO and at the Same Time  Auxiliary contactor (KT) in Delta Coil Circuit(4) change its Position from NO To NC so Delta coil energized and  Delta Main Contactor becomes NO To NC. Now Motor terminal connection change from star to delta connection.

A normally close auxiliary contact from both star and delta contactors (5&6)are also placed opposite of both star and delta contactor coils, these interlock contacts serves as safety switches to prevent simultaneous activation of both star and delta contactor coils, so that one cannot be activated without the other deactivated first. Thus, the delta contactor coil cannot be active when the star contactor coil is active, and similarly, the star contactor coil cannot also be active while the delta contactor coil is active.

The control circuit above also provides two interrupting contacts to shutdown the motor. The OFF push button switch break the control circuit and the motor when necessary. The thermal overload contact is a protective device which automatically opens the STOP Control circuit in case when motor overload current is detected by the thermal overload relay, this is to prevent burning of the motor in case of excessive load beyond the rated capacity of the motor is detected by the thermal overload relay.

At some point during starting it is necessary to change from a star connected winding to a delta connected winding. Power and control circuits can be arranged to this in one of two ways – open transition or closed transition.

Open Transition Starter

Discuss mention above is called open transition switching because there is an open state between the star state and the delta state.

In open transition the power is disconnected from the motor while the winding are reconfigured via external switching.

When a motor is driven by the supply, either at full speed or at part speed, there is a rotating magnetic field in the stator. This field is rotating at line frequency. The flux from the stator field induces a current in the rotor and this in turn results in a rotor magnetic field.

When the motor is disconnected from the supply (open transition) there is a spinning rotor within the stator and the rotor has a magnetic field. Due to the low impedance of the rotor circuit, the time constant is quite long and the action of the spinning rotor field within the stator is that of a generator which generates voltage at a frequency determined by the speed of the rotor.

Note:
When the motor is reconnected to the supply, it is reclosing onto an unsynchronized generator and this result in a very high current and torque transient. The magnitude of the transient is dependent on the phase relationship between the generated voltage and the line voltage at the point of closure can be much higher than DOL current and torque and can result in electrical and mechanical damage.

Open transition starting is the easiest to implement in terms or cost and circuitry and if the timing of the changeover is good, this method can work well. In practice though it is difficult to set the necessary timing to operate correctly and disconnection/reconnection of the supply can cause significant voltage/current transients.

Four states of open transition

OFF State: All Contactors are open.

Star State: The Main [KM3] and the Star [KM1] contactors are closed and the delta [KM2] contactor is open. The motor is connected in star and will produce one third of DOL torque at one third of DOL current.

Open State: This type of operation is called open transition switching because there is an open state between the star state and the delta state. The Main contractor is closed and the Delta and Star contactors are open. There is voltage on one end of the motor windings, but the other end is open so no current can flow. The motor has a spinning rotor and behaves like a generator.

Delta State: The Main and the Delta contactors are closed. The Star contactor is open. The motor is connected to full line voltage and full power and torque are available

Closed Transition Star-Delta Starter

There is a technique to reduce the magnitude of the switching transients. This requires the use of a fourth contactor and a set of three resistors. The resistors must be sized such that considerable current is able to flow in the motor windings while they are in circuit.

The auxiliary contactor and resistors are connected across the delta contactor. In operation, just before the star contactor opens, the auxiliary contactor closes resulting in current flow via the resistors into the star connection. Once the star contactor opens, current is able to flow round through the motor windings to the supply via the resistors. These resistors are then shorted by the delta contactor.

If the resistance of the resistors is too high, they will not swamp the voltage generated by the motor and will serve no purpose.

This is achieved by introducing resistors to take up the current flow during the winding changeover. A fourth contractor is required to place the resistor in circuit before opening the star contactor and then removing the resistors once the delta contactor is closed.

These resistors need to be sized to carry the motor current. In addition to requiring more switching devices, the control circuit is more complicated due to the need to carry out resistor switching.

 Five states of closed transition

OFF State. All Contactors are open

Star State. The Main [KM3] and the Star [KM1] contactors are closed and the delta [KM2] contactor is open. The motor is connected in star and will produce one third of DOL torque at one third of DOL current.

Star Transition State. The motor is connected in star and the resistors are connected across the delta contactor via the aux [KM4] contactor.

Closed Transition State. The Main [KM3] contactor is closed and the Delta [KM2] and Star [KM1] contactors are open. Current flows through the motor windings and the transition resistors via KM4.

Delta State. The Main and the Delta contactors are closed. The transition resistors are shorted out. The Star contactor is open. The motor is connected to full line voltage and full power and torque are available.

Reason Behind Using Star Delta 

We use star delta which, is also called wye delta in north America, to reduce the inrush current when the motor starts. When large induction motors start in delta their starting current can be over 5 times higher than the full load current which occurs when the motor stabilises and runs normally.

This huge surge in current can cause lots of problems. The buildings electrical system will be hit by this sudden large demand. The electrical infrastructure will rapidly increase in temperature leading to component failure and even electrical fires. The sudden demand also causes voltage drops throughout the buildings electrical system which we can visually see because the lights will dip, this can cause many problems for things such as computers and servers.

So to reduce the starting current we simply need to reduce the starting voltage.

The star configuration will reduce the coil voltage to around 58% compared to the delta configuration. A lower voltage will lead to a lower current. The current in the coil while in star configuration will be around ~33% of the delta configuration. This will also lead to a reduction in torque, the star configuration torque will also be around 33% compared to delta.

Inside Operation With Basic Example

Let consider we have the motor connected in delta with  supply voltage of 400V.

insdie operation


If we measure across the two ends of a coil, we again measure the line to line voltage of 400V. Let say each coil has a resistance, or impedance as this is AC power, of 20 Ohms. That means we will get a current reading on the coil of 20 Amp. We can calculate that from 400V / 20 Ohms = 20A. But the current in the line will be different, it will be 34.6A and we get that from 20A x sqr3 = 34.6A


inside operation

If we then looked at a star connection. We again have a line to line voltage of 400V, if we measure between any two phases. But, with the star connection all our coils meet at the star point or neutral point. We can run a neutral line from this point. So When we measure the voltage across the ends of the coil, we get a lower value of 230V, that’s because the coil isn’t directly connected between two phases like the delta version. One end is connected to a phase, the other end is connected to a shared point, so the voltage is therefore shared and will be less because one of the phases is always is reverse.


We can see the 230V reading by dividing the 400V by sqr3 = 230V. As the voltage is less the current will be too. If the coil is again 20ohms of resistance, or impedance, then the current is calculated by 230V / 20ohms which is 11.5Amp. The current in the line will also be 11.5A.

So with the delta connection the coil is exposed to the full 400V between two phases. But the star connection is only exposed to 230V between the phase and neutral. So we can see that the star uses less voltage and therefore less current compared to the delta version, which is why we use it first.

Features

  1. For low- to high-power three-phase motors.
  2. Reduced starting current
  3. Six connection cables
  4. Reduced starting torque
  5. Current peak on changeover from star to delta
  6. Mechanical load on changeover from star to delta

Advantages

  1. The operation of the star-delta method is simple and rugged
  2. It is relatively cheap compared to other reduced voltage methods.
  3. Good Torque/Current Performance.
  4. It draws 2 times starting current of the full load ampere of the motor connected

No comments:

Post a Comment